Why do I get the lower energy usage when I raise the minimum temperature of the supply air? |
Usually gives increased supply air temperature increased energy then supply air is heated in spite of the fact that the room temperature is higher than the requirement. But if the supply air temperature is achieved mainly by increased heat recovery it causes an increased use of recovery. It results in increased room temperature over minimum level. The heat stored in the building and heating other time decreases. |
How to calculate natural ventilation. |
When it comes to energy calculation, it is usually most appropriate to adopt that ventilation requirements are achieved regardless of the system type. It is usually less interesting to note that energy savings is achieved by not fulfilling the ventilation requirements. It is calculated with exhaust air ventilation. Power to the fan is set to zero by setting fan pressure to zero. Complement with fresh air vents so that the internal negative pressure is set at levels that can be operated with natural ventilation IE max 5-10 Pa depending on chimney height. |
How do you handle airing? |
In Sveby data input guide for residential project there are different suggestions on how to handle the airing. We recommend adding a little air flow in addition to normal ventilation. A ventilation unit can be called "Airing" where to place airing ventilation flows for supply and extract. We advise against an energy supplement. It can never be "right" because it does not take into account solar collectors, heat pumps or a number of other factors that affect energy use. |
How to simulate a Crawl Space. |
In most cases, a crawl space can be calculated as slab on grade. Although it is fresh air ventilated so is the ventilation is usually rather limited. To be more precise the crawl space is calculated as a separate zone. The temperature requirements are set widely enough to get no heating or cooling. Add fresh air vents. |
How to simulate an exhaust air ventilated crawl space. |
Calculate the space as a separate zone. Insert a ventilation unit and put the building's exhaust fan as supply air fan in crawl space zone to get the heat from the fan to the crawl space. Exhaust air from the crawl space is simulated according to actual performance with or without fan. |
How do I change the language in VIPS-Energy? |
Click at code/language under menu choice “Input”. |